Match the source to the heat user

Measure both sides over representative periods before you size storage or sign a heat-offtake agreement. For each pair, establish:

  • Factory cooling → process water: fluid quality, available flow, shift profile, and the required hot-water supply and return temperatures.
  • Building cooling → space heating and domestic hot water: coincident loads, seasonal storage, final hot-water temperature and backup heat.
  • Data-centre cooling → heating network: actual liquid-loop temperatures, the cooling reliability requirement, the heat-offtake profile and the network return temperature.

Data-centre heat recovery

This section is design guidance; it does not describe an Energy Machines data-centre installation.

Start with the temperatures and flows actually available at the cooling interface. An intermediate loop adds an approach temperature and pumping energy.

Cooling comes first. It must continue when the heat pump or the heat user is unavailable, so design backup heat rejection, isolation and controls around the data centre’s cooling reliability requirement.

Find out who takes the heat in summer, at what return temperature and for how many hours. A constant IT cooling load does not mean constant heat sales.

Reference installations

Sønderjylland Hospital covers its heating and cooling from its own waste heat and exports the surplus to district heating. The Sandvik Coromant factory stores production waste heat in a borehole thermal energy store.

Models and documented rating conditions

Rating points as printed in each datasheet. They describe one operating case each, not the operating envelope. Where a datasheet omits the electrical boundary, load or speed, the row says so.

Temperatures are fluid inlet → outlet in °C, capacity in kW. Compare rows only at the same temperatures and boundary.
Model / refrigerantSource inlet → outletHeated water inlet → outletDeclared dutyThermal capacity / COPDocument / boundary
EMF 2140-2-8
R290
ethanol 26%
1 → -3 °C
water
47 → 53 °C
Heating
60 Hz
Load: Not stated
No subcooler / standard configuration
Not stated
COP: Withheld pending confirmation
Datasheet V3.0 · 2026-03-06 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMF 2140-2-8
R290
ethanol 26%
1 → -3 °C
water
47 → 53 °C
Heating
140 Hz
Load: Not stated
No subcooler / standard configuration

Endpoint of the printed 30–140 Hz range; confirm interpretation for project selection.

107 kW
COP: Withheld pending confirmation
Datasheet V3.0 · 2026-03-06 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMF 2220-2-8
R290
ethanol 26%
1 → -3 °C
water
47 → 53 °C
Heating
60 Hz
Load: Not stated
No subcooler / standard configuration
Not stated
COP: Withheld pending confirmation
Datasheet V3.0 · 2026-03-06 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMF 2220-2-8
R290
ethanol 26%
1 → -3 °C
water
47 → 53 °C
Heating
140 Hz
Load: Not stated
No subcooler / standard configuration

Endpoint of the printed 30–140 Hz range; confirm interpretation for project selection.

164 kW
COP: Withheld pending confirmation
Datasheet V3.0 · 2026-03-06 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMHP 36-36-2-4
R1234ze
ethanol 26%
1 → -3 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
85 kW
COP: Withheld pending confirmation
Datasheet V7.0 · 2026-03-05 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMHP 36-36-2-7
R515B
ethanol 26%
1 → -3 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
85 kW
COP: Withheld pending confirmation
Datasheet V7.0 · 2026-03-05 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMHP 36F-36F-2-4
R1234ze
ethanol 26%
1 → -3 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
100 kW
COP: Withheld pending confirmation
Datasheet V7.0 · 2026-03-05 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMHP 36F-36F-2-7
R515B
ethanol 26%
1 → -3 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
100 kW
COP: Withheld pending confirmation
Datasheet V7.0 · 2026-03-05 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMHP 44-44-2-4
R1234ze
ethanol 26%
1 → -3 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
98 kW
COP: Withheld pending confirmation
Datasheet V7.0 · 2026-03-05 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMHP 44-44-2-7
R515B
ethanol 26%
1 → -3 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
98 kW
COP: Withheld pending confirmation
Datasheet V7.0 · 2026-03-05 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMHP 44F-44F-2-4
R1234ze
ethanol 26%
1 → -3 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
116 kW
COP: Withheld pending confirmation
Datasheet V7.0 · 2026-03-05 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMHP 44F-44F-2-7
R515B
ethanol 26%
1 → -3 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
116 kW
COP: Withheld pending confirmation
Datasheet V7.0 · 2026-03-05 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMHP 60-60-2-4
R1234ze
ethanol 26%
1 → -3 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
135 kW
COP: Withheld pending confirmation
Datasheet V7.0 · 2026-03-05 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMHP 60-60-2-7
R515B
ethanol 26%
1 → -3 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
135 kW
COP: Withheld pending confirmation
Datasheet V7.0 · 2026-03-05 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMHP 60F-60F-2-4
R1234ze
ethanol 26%
1 → -3 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
161 kW
COP: Withheld pending confirmation
Datasheet V7.0 · 2026-03-05 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMHP 60F-60F-2-7
R515B
ethanol 26%
1 → -3 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
161 kW
COP: Withheld pending confirmation
Datasheet V7.0 · 2026-03-05 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMHP 80-80-2-4
R1234ze
ethanol 26%
1 → -3 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
181 kW
COP: Withheld pending confirmation
Datasheet V7.0 · 2026-03-05 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMHP 80-80-2-7
R515B
ethanol 26%
1 → -3 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
181 kW
COP: Withheld pending confirmation
Datasheet V7.0 · 2026-03-05 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMHP 80F-80F-2-4
R1234ze
ethanol 26%
1 → -3 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
216 kW
COP: Withheld pending confirmation
Datasheet V7.0 · 2026-03-05 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMHP 80F-80F-2-7
R515B
ethanol 26%
1 → -3 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
216 kW
COP: Withheld pending confirmation
Datasheet V7.0 · 2026-03-05 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMT 1230-1-4-ECO
R1234ze
water
12 → 7 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
265 kW
COP: Withheld pending confirmation
Datasheet V1.8 · 2025-12-04 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMT 1230-1-7-ECO
R515B
water
12 → 7 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
265 kW
COP: Withheld pending confirmation
Datasheet V1.8 · 2025-12-04 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMT 1285-1-4-ECO
R1234ze
water
12 → 7 °C
water
57 → 63 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
347 kW
COP: Withheld pending confirmation
Datasheet V1.8 · 2025-12-04 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMT 1285-1-7-ECO
R515B
water
12 → 7 °C
water
57 → 63 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
347 kW
COP: Withheld pending confirmation
Datasheet V1.8 · 2025-12-04 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMT 1310-1-4-ECO
R1234ze
water
12 → 7 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
379 kW
COP: Withheld pending confirmation
Datasheet V1.8 · 2025-12-04 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMT 1310-1-7-ECO
R515B
water
12 → 7 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
379 kW
COP: Withheld pending confirmation
Datasheet V1.8 · 2025-12-04 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMT 1380-1-4-ECO
R1234ze
water
12 → 7 °C
water
57 → 63 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
476 kW
COP: Withheld pending confirmation
Datasheet V1.8 · 2025-12-04 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMT 1380-1-7-ECO
R515B
water
12 → 7 °C
water
57 → 63 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
476 kW
COP: Withheld pending confirmation
Datasheet V1.8 · 2025-12-04 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMT 1490-1-4-ECO
R1234ze
water
12 → 7 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
589 kW
COP: Withheld pending confirmation
Datasheet V1.8 · 2025-12-04 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMT 1490-1-7-ECO
R515B
water
12 → 7 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
589 kW
COP: Withheld pending confirmation
Datasheet V1.8 · 2025-12-04 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMT 2230-1-4-FT
R1234ze
water
12 → 7 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
530 kW
COP: Withheld pending confirmation
Datasheet V1.8 · 2025-12-04 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMT 2230-1-7-FT
R515B
water
12 → 7 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
530 kW
COP: Withheld pending confirmation
Datasheet V1.8 · 2025-12-04 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMT 2230-2-4-ECO
R1234ze
water
12 → 7 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
530 kW
COP: Withheld pending confirmation
Datasheet V1.8 · 2025-12-04 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMT 2230-2-7-ECO
R515B
water
12 → 7 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
530 kW
COP: Withheld pending confirmation
Datasheet V1.8 · 2025-12-04 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMT 2285-1-4-FT
R1234ze
water
12 → 7 °C
water
57 → 63 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
694 kW
COP: Withheld pending confirmation
Datasheet V1.7 · 2024-12-23 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMT 2285-1-7-FT
R515B
water
12 → 7 °C
water
57 → 63 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
694 kW
COP: Withheld pending confirmation
Datasheet V1.7 · 2024-12-23 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMT 2285-2-4-ECO
R1234ze
water
12 → 7 °C
water
57 → 63 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
694 kW
COP: Withheld pending confirmation
Datasheet V1.7 · 2024-12-23 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMT 2285-2-7-ECO
R515B
water
12 → 7 °C
water
57 → 63 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
694 kW
COP: Withheld pending confirmation
Datasheet V1.7 · 2024-12-23 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMT 2310-1-4-FT
R1234ze
water
12 → 7 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
758 kW
COP: Withheld pending confirmation
Datasheet V1.7 · 2024-12-23 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMT 2310-1-7-FT
R515B
water
12 → 7 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
758 kW
COP: Withheld pending confirmation
Datasheet V1.7 · 2024-12-23 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMT 2310-2-4-ECO
R1234ze
water
12 → 7 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
758 kW
COP: Withheld pending confirmation
Datasheet V1.7 · 2024-12-23 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMT 2310-2-7-ECO
R515B
water
12 → 7 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
758 kW
COP: Withheld pending confirmation
Datasheet V1.7 · 2024-12-23 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMT 2380-1-4-FT
R1234ze
water
12 → 7 °C
water
57 → 63 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
951 kW
COP: Withheld pending confirmation
Datasheet V1.7 · 2024-12-23 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMT 2380-1-7-FT
R515B
water
12 → 7 °C
water
57 → 63 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
951 kW
COP: Withheld pending confirmation
Datasheet V1.7 · 2024-12-23 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMT 2380-2-4-ECO
R1234ze
water
12 → 7 °C
water
57 → 63 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
951 kW
COP: Withheld pending confirmation
Datasheet V1.7 · 2024-12-23 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMT 2380-2-7-ECO
R515B
water
12 → 7 °C
water
57 → 63 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
951 kW
COP: Withheld pending confirmation
Datasheet V1.7 · 2024-12-23 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMT 2490-1-4-FT
R1234ze
water
12 → 7 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
1,178 kW
COP: Withheld pending confirmation
Datasheet V1.7 · 2024-12-23 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMT 2490-1-7-FT
R515B
water
12 → 7 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
1,178 kW
COP: Withheld pending confirmation
Datasheet V1.7 · 2024-12-23 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMT 2490-2-4-ECO
R1234ze
water
12 → 7 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
1,178 kW
COP: Withheld pending confirmation
Datasheet V1.7 · 2024-12-23 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMT 2490-2-7-ECO
R515B
water
12 → 7 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
1,178 kW
COP: Withheld pending confirmation
Datasheet V1.7 · 2024-12-23 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMT 3285-1-4-FT
R1234ze
water
12 → 7 °C
water
57 → 63 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
1,041 kW
COP: Withheld pending confirmation
Datasheet V1.8 · 2025-12-04 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMT 3285-1-7-FT
R515B
water
12 → 7 °C
water
57 → 63 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
1,041 kW
COP: Withheld pending confirmation
Datasheet V1.8 · 2025-12-04 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMT 4230-1-4-FT
R1234ze
water
12 → 7 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
1,060 kW
COP: Withheld pending confirmation
Datasheet V1.7 · 2024-12-23 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMT 4230-1-7-FT
R515B
water
12 → 7 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
1,060 kW
COP: Withheld pending confirmation
Datasheet V1.7 · 2024-12-23 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMT 4285-1-4-FT
R1234ze
water
12 → 7 °C
water
57 → 63 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
1,388 kW
COP: Withheld pending confirmation
Datasheet V1.7 · 2024-12-23 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMT 4285-1-7-FT
R515B
water
12 → 7 °C
water
57 → 63 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
1,388 kW
COP: Withheld pending confirmation
Datasheet V1.7 · 2024-12-23 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMT 4310-1-4-FT
R1234ze
water
12 → 7 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
1,516 kW
COP: Withheld pending confirmation
Datasheet V1.7 · 2024-12-23 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMT 4310-1-7-FT
R515B
water
12 → 7 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
1,516 kW
COP: Withheld pending confirmation
Datasheet V1.7 · 2024-12-23 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMT 4380-1-4-FT
R1234ze
water
12 → 7 °C
water
57 → 63 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
1,902 kW
COP: Withheld pending confirmation
Datasheet V1.7 · 2024-12-23 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMT 4380-1-7-FT
R515B
water
12 → 7 °C
water
57 → 63 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
1,902 kW
COP: Withheld pending confirmation
Datasheet V1.7 · 2024-12-23 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMT 4490-1-4-FT
R1234ze
water
12 → 7 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
2,356 kW
COP: Withheld pending confirmation
Datasheet V1.7 · 2024-12-23 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMT 4490-1-7-FT
R515B
water
12 → 7 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
2,356 kW
COP: Withheld pending confirmation
Datasheet V1.7 · 2024-12-23 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated

Related