EMT

1490-1-4-ECO

Product Family:
EMT
Certification:
CE
Refrigerant Type:
R1234ze
Safety Class:
A2L
Capacity Control:
Frequency controlled

Application

Nominal Heating Capacity:
589 kW
Nominal Cooling Capacity:
515 kW
Nominal COP Heating:
4.47
Nominal COP Cooling:
3.91
Condenser Outlet Temp.:
55 °C
Evaporator Inlet Temp.:
0 °C
Lowest Evaporator Temp. To Reach Highest Condenser Temp.:
7 °C
Highest Evaporator Outlet Temp.:
30 °C

Dimensions

Length:
2950 mm
Width:
1210 mm
Height:
1945 mm
Weight:
3300 kg

Technical Features

Compressor Type:
Turbo
Energy Source:
Waste heat, Water
Special Features:
Economizer, Oil-free
GWP:
1.37

This Energy Machines™ EMT model contains a refrigerant circuit with an oil-free centrifugal compressor. It is classified as a non-positive displacement compressor.

This model is equipped with an economizer heat exchanger, increasing its energy efficiency. The machine’s evaporator and condenser are shell-and-tube heat exchangers. The evaporator operates with a flooded evaporation technique.

These components work together to create a powerful and efficient machine.

Documentation

Check an operating point

Indicative — engineering review
Cold side (source)
Hot side (sink)
Up to date

Operating envelope

-10 °C-5 °C0 °C5 °C10 °C15 °C20 °C25 °C30 °C20 °C30 °C40 °C50 °C60 °CTe – evaporating temperatureTc – condensing temperatureCOP 4COP 5COP 6COP 7COP 8COP 9COP 10COP 111COP 4.47 · 589 kW

Operating points

Columns
Inputs
Results
Remembered in this browser.
PointSource in → outSink in → outLoadTe / TcHeating capacityElectrical inputCOP heatingActions
110.0 → 7.0 °C40.0 → 45.0 °C100 %4.0 / 48.0 °C589 kW132 kW4.47
Indicative values. Engineering review required.

The EMT 1490-1-4-ECO is a turbo-compressor heat pump on R1234ze (safety class A2L). Catalogue nominal heating capacity: 589 kW. Catalogue maximum condenser outlet: 55 °C (not verified by this datasheet).

Need an A1 refrigerant? The EMT 1490-1-7-ECO is the R515B variant. Both share one datasheet performance table, which shows no performance advantage for either. Confirm site and safety requirements with engineering.

Rating conditions

Rating conditions
Mode / configurationSource fluid in → outSink fluid in → outSpeed / load pointCapacityElectrical input / boundaryCOPDatasheet revision
Datasheet rating points are awaiting engineering confirmation. Request a confirmed operating point for your project.

Source is the evaporator side and sink the condenser side, in both modes. Electrical input is compressor power at the rated point, not the value for sizing the supply. The datasheet names no test standard and no simultaneous heating-and-cooling rating.