EMF

2140-2-8

Product Family:
EMF
Certification:
CE
Refrigerant Type:
R290
Safety Class:
A3
Capacity Control:
Frequency controlled

Application

Nominal Heating Capacity:
107 kW
Nominal Cooling Capacity:
124 kW
Nominal COP Heating:
2.68
Nominal COP Cooling:
3.38
Condenser Outlet Temp.:
77 °C
Evaporator Inlet Temp.:
-20 °C
Lowest Evaporator Temp. To Reach Highest Condenser Temp.:
-10 °C
Highest Evaporator Outlet Temp.:
25 °C

Dimensions

Length:
1050 mm
Width:
795 mm
Height:
1743 mm
Weight:
650 kg

Technical Features

Compressor Type:
Scroll
Energy Source:
Ground, Waste heat, Water
Special Features:
High capacity control range
GWP:
0.02

The Energy Machines™ EMF model combines efficiency, capacity modulation, and installation flexibility. Its two independent refrigerant circuits use natural refrigerants together with scroll compressors and frequency inverters to deliver excellent part-load performance and dependable capacity. The EMF model is specifically designed for heating and cooling applications.

Each circuit carries a refrigerant charge below 5 kg, supporting more flexible installation options.

With integrated controls for the circulation pumps and control valves, the EMF comes as a complete heat pump and cooling system in a single unit.

Documentation

Check an operating point

Indicative — engineering review
Cold side (source)
Hot side (sink)
Up to date

Operating envelope

-30 °C-25 °C-20 °C-15 °C-10 °C-5 °C0 °C5 °C10 °C15 °C20 °C25 °C20 °C30 °C40 °C50 °C60 °C70 °C80 °CTe – evaporating temperatureTc – condensing temperatureCOP 2COP 3COP 4COP 5COP 61COP 2.68 · 107 kW

Operating points

Columns
Inputs
Results
Remembered in this browser.
PointSource in → outSink in → outLoadTe / TcHeating capacityElectrical inputCOP heatingActions
110.0 → 7.0 °C40.0 → 45.0 °C100 %4.0 / 48.0 °C107 kW40 kW2.68
Indicative values. Engineering review required.

The EMF 2140-2-8 is a scroll-compressor heat pump on R290 (safety class A3). It delivers 107 kW of heat at 1 °C → -3 °C ethanol 26% on the source side and 47 °C → 53 °C water on the sink side, at 140 Hz. Catalogue maximum condenser outlet: 77 °C (not verified by this datasheet).

Rating conditions

6 rated points · datasheet V3.0

Rated points from datasheet V3.0 (2026-03-06). These are rating conditions, not operating limits.

Rating conditions
Mode / configurationSource fluid in → outSink fluid in → outSpeed / load pointCapacityElectrical input / boundaryCOPDatasheet revision
Heating
Standard
ethanol 26%
1 °C → -3 °C
water
47 °C → 53 °C
30 Hz11 kWNot stated
Not stated
Not statedV3.0
2026-03-06
Heating
Standard
ethanol 26%
1 °C → -3 °C
water
47 °C → 53 °C
60 HzNot statedNot stated
Not stated
2.93V3.0
2026-03-06
Heating
Standard
ethanol 26%
1 °C → -3 °C
water
47 °C → 53 °C
140 Hz107 kWNot stated
Not stated
2.68V3.0
2026-03-06
Cooling
Standard
ethanol 26%
15 °C → 10 °C
water
37 °C → 43 °C
30 Hz14 kWNot stated
Not stated
Not statedV3.0
2026-03-06
Cooling
Standard
ethanol 26%
15 °C → 10 °C
water
37 °C → 43 °C
60 HzNot statedNot stated
Not stated
4.42V3.0
2026-03-06
Cooling
Standard
ethanol 26%
15 °C → 10 °C
water
37 °C → 43 °C
140 Hz124 kWNot stated
Not stated
3.38V3.0
2026-03-06

Source is the evaporator side and sink the condenser side, in both modes. Electrical input is the power at the rated point within the boundary named in each row, not the value for sizing the supply. The datasheet names no test standard and no simultaneous heating-and-cooling rating. Values the datasheet leaves blank are not calculated from COP.