Equipment COP and system COP

Illustrative figures, not an Energy Machines rating: a heat pump delivers 400 kW of heat with 100 kW of electrical input at one fixed operating case. Equipment COP = 400 / 100 = 4.0. If the source and distribution pumps draw another 20 kW, system COP = 400 / (100 + 20) ≈ 3.3.

In a real calculation, take every power at the same temperatures and load. The rated power input given for electrical connection sizing is not the input at a duty point; do not use it as the COP denominator.

The EMB points in the table below state heating capacity, compressor electrical input and COP at the same operating case. Their boundary is the compressors only; add pumps and auxiliaries before you compare them with a system COP.

Temperature lift and part load

Temperature lift is the difference between the refrigerant condensing and evaporating temperatures. It is larger than the difference between the fluid temperatures, because each heat exchanger adds an approach. More lift means more compressor work per kW of heat, so COP falls as supply temperature rises or source temperature drops.

The ideal (Carnot) COP uses absolute refrigerant temperatures and gives a theoretical upper bound. It does not replace declared or measured performance.

Part load is operation below design output. Ask for the minimum stable capacity and how several units are sequenced.

Comparing datasheets and seasonal figures

Compare COPs only at the same fluid temperatures, flows, fluid composition, load or speed, and configuration. Check whether the electrical input covers the compressors only or also drives, controls and pumps.

SCOP and SPF are seasonal figures. Each needs a stated calculation method, climate or load profile and auxiliary-energy boundary, and a SCOP from one method does not describe every industrial installation. An annual figure comes from time-weighted energy, not from averaging a few COP points.

Models and documented rating conditions

Rating points as printed in each datasheet. They describe one operating case each, not the operating envelope. Where a datasheet omits the electrical boundary, load or speed, the row says so.

Temperatures are fluid inlet → outlet in °C, capacity in kW. Compare rows only at the same temperatures and boundary.
Model / refrigerantSource inlet → outletHeated water inlet → outletDeclared dutyThermal capacity / COPDocument / boundary
EMB 2295-1-4
R1234ze
ethanol 26%
1 → -3 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
114 kW
COP: Withheld pending confirmation
Datasheet V3.1 · 2026-06-04 · EN · p. 2
Electrical input: 41.5 kW (compressors only)
COP scope: compressors only
Test standard: Not stated
EMB 2295-1-7
R515B
ethanol 26%
1 → -3 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
114 kW
COP: Withheld pending confirmation
Datasheet V3.1 · 2026-06-04 · EN · p. 2
Electrical input: 41.5 kW (compressors only)
COP scope: compressors only
Test standard: Not stated
EMB 2387-1-4
R1234ze
ethanol 26%
1 → -3 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
145 kW
COP: 2.84
Datasheet V3.1 · 2026-06-04 · EN · p. 2
Electrical input: 51.3 kW (compressors only)
COP scope: compressors only
Test standard: Not stated
EMB 2387-1-7
R515B
ethanol 26%
1 → -3 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
145 kW
COP: 2.84
Datasheet V3.1 · 2026-06-04 · EN · p. 2
Electrical input: 51.3 kW (compressors only)
COP scope: compressors only
Test standard: Not stated
EMB 2480-1-4
R1234ze
ethanol 26%
1 → -3 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
175 kW
COP: 2.87
Datasheet V3.1 · 2026-06-04 · EN · p. 2
Electrical input: 61 kW (compressors only)
COP scope: compressors only
Test standard: Not stated
EMB 2480-1-7
R515B
ethanol 26%
1 → -3 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
175 kW
COP: 2.87
Datasheet V3.1 · 2026-06-04 · EN · p. 2
Electrical input: 61 kW (compressors only)
COP scope: compressors only
Test standard: Not stated
EMB 4295-2-4
R1234ze
ethanol 26%
1 → -3 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
229 kW
COP: Withheld pending confirmation
Datasheet V3.1 · 2026-06-04 · EN · p. 2
Electrical input: 83 kW (compressors only)
COP scope: compressors only
Test standard: Not stated
EMB 4295-2-7
R515B
ethanol 26%
1 → -3 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
229 kW
COP: Withheld pending confirmation
Datasheet V3.1 · 2026-06-04 · EN · p. 2
Electrical input: 83 kW (compressors only)
COP scope: compressors only
Test standard: Not stated
EMB 4387-2-4
R1234ze
ethanol 26%
1 → -3 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
289 kW
COP: Withheld pending confirmation
Datasheet V3.1 · 2026-06-04 · EN · p. 2
Electrical input: 102.5 kW (compressors only)
COP scope: compressors only
Test standard: Not stated
EMB 4387-2-7
R515B
ethanol 26%
1 → -3 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
289 kW
COP: Withheld pending confirmation
Datasheet V3.1 · 2026-06-04 · EN · p. 2
Electrical input: 102.5 kW (compressors only)
COP scope: compressors only
Test standard: Not stated
EMB 4480-2-4
R1234ze
ethanol 26%
1 → -3 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
350 kW
COP: 2.87
Datasheet V3.1 · 2026-06-04 · EN · p. 2
Electrical input: 122.1 kW (compressors only)
COP scope: compressors only
Test standard: Not stated
EMB 4480-2-7
R515B
ethanol 26%
1 → -3 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
350 kW
COP: 2.87
Datasheet V3.1 · 2026-06-04 · EN · p. 2
Electrical input: 122.1 kW (compressors only)
COP scope: compressors only
Test standard: Not stated