Heat pump range
EMHP
Reciprocating heat pumps for higher-temperature heat delivery
EMHP is the reciprocating-compressor range for higher supply temperatures, such as process heat and district heating. It comes on R1234ze or R515B.
What the range covers
- Nominal heating capacity
- 85–216 kW
- Maximum condenser outlet temperature
- 90 °C
- Lowest source inlet temperature
- -5 °C
- Refrigerants
- R1234ze, R515B
- Compressor type
- Reciprocating
- Capacity control
- Frequency controlled, PWM
These are the extremes across the range. No single model reaches all of them.
Where EMHP fits
Heating
Cooling
DHW
High temperature
- Process hot-water and industrial heat supply
- District heating integration and temperature boosting
- Recovery and upgrading of process waste heat
EMHP models
16 models from 85 to 216 kW heating. Simulation opens with the EMHP machines to choose from. Enter your temperatures and capacity there to see which models cover them.
Find a model for your operating points
Technology
Compressor technology: reciprocating, high temperature
EMHP uses reciprocating compressors with frequency control and PWM capacity regulation, built for high temperature lift. The published maximum condenser outlet temperature is 90 °C.
Efficiency falls as temperature lift rises. Set the supply temperature to what the process actually needs.
Key facts
- Reciprocating compressors for high temperature lift
- Frequency control and PWM capacity regulation
- Published maximum condenser outlet temperature: 90 °C
- R1234ze (A2L) or R515B (A1)
More about the EMHP range
Size and scale
Drawn to scale from the published dimensions. Weights and service clearances are on each model's datasheet.

- Shown
- 60-60-2-4
- H × L × W
- 1,845 × 1,970 × 875 mm
- Person for scale
- 1,800 mm
Machine views
Angled view
Are the printed COP values whole-unit ratings?
No whole-unit COP is printed. The datasheet gives COP per circuit, in columns C1 and C2, and the total capacities separately, with no electrical input at the rated point. Ask us to confirm the scope before you select on these figures.
What do the EMHP datasheets leave out?
The performance tables do not give the electrical input at the rated point, the compressor speed or load, or the test standard. The electrical sizing power and supply frequency on the datasheet are for sizing the supply; they are not rated figures. Ask us for these before you fix a design.
R1234ze or R515B?
Choose by the safety class your project allows: R1234ze is A2L, R515B is A1. The datasheets list the same performance for both.
- Selecting a heat pump for 90 °C hot water
- Heat pumps for district heating
- How to read our ratingsWhat the rated figures include, and why rated temperatures are not operating limits.