EMHP

44F-44F-2-7

Product Family:
EMHP
Certification:
CE
Refrigerant Type:
R515B
Safety Class:
A1
Capacity Control:
Frequency controlled, PWM

Application

Nominal Heating Capacity:
116 kW
Nominal Cooling Capacity:
162 kW
Nominal COP Heating:
3.14
Nominal COP Cooling:
3.72
Condenser Outlet Temp.:
90 °C
Evaporator Inlet Temp.:
-5 °C
Lowest Evaporator Temp. To Reach Highest Condenser Temp.:
0 °C
Highest Evaporator Outlet Temp.:
35 °C

Dimensions

Length:
1970 mm
Width:
875 mm
Height:
1845 mm
Weight:
1650 kg

Technical Features

Compressor Type:
Reciprocating
Energy Source:
Ground, Waste heat, Water
Special Features:
Frequency option, High capacity control range, Internal pumps
GWP:
293

This Energy Machines™ EMHP model contains two refrigerant circuits with a semi-hermetic reciprocating compressor in each. Together with frequency inverters, the EMHP model has the capability of providing either high turndown or extra capacity when required. The two refrigerant circuits are completely independent, ensuring the stability of the heating supply.

The EMHP model is specifically designed for heating and cooling purposes. It can handle large pressure drops on the water side using the machine’s internal water pumps.

The EMHP comes as a complete heat pump and cooling system in one unit.

Documentation

Check an operating point

Indicative — engineering review
Cold side (source)
Hot side (sink)
Up to date

Operating envelope

-15 °C-10 °C-5 °C0 °C5 °C10 °C15 °C20 °C25 °C30 °C35 °C20 °C30 °C40 °C50 °C60 °C70 °C80 °C90 °C100 °CTe – evaporating temperatureTc – condensing temperatureCOP 2COP 3COP 4COP 5COP 6COP 71COP 3.14 · 116 kW

Operating points

Columns
Inputs
Results
Remembered in this browser.
PointSource in → outSink in → outLoadTe / TcHeating capacityElectrical inputCOP heatingActions
110.0 → 7.0 °C40.0 → 45.0 °C100 %4.0 / 48.0 °C116 kW37 kW3.14
Indicative values. Engineering review required.

The EMHP 44F-44F-2-7 is a reciprocating-compressor heat pump on R515B (safety class A1). Catalogue nominal heating capacity: 116 kW. Catalogue maximum condenser outlet: 90 °C (not verified by this datasheet).

Does the project accept an A2L refrigerant? The EMHP 44F-44F-2-4 is the R1234ze variant. Both share one datasheet performance table, which shows no performance advantage for either. Confirm site and safety requirements with engineering.

Rating conditions

Rating conditions
Mode / configurationSource fluid in → outSink fluid in → outSpeed / load pointCapacityElectrical input / boundaryCOPDatasheet revision
Datasheet rating points are awaiting engineering confirmation. Request a confirmed operating point for your project.

Source is the evaporator side and sink the condenser side, in both modes. Electrical input is compressor power at the rated point, not the value for sizing the supply. The datasheet names no test standard and no simultaneous heating-and-cooling rating.