Heat pump range
EMF
Natural-refrigerant heat pumps for demanding source conditions
EMF is the propane (R290) range, for projects that call for a natural refrigerant and have low source temperatures. Refrigerant safety, plant-room layout and the source side are designed for each installation.
What the range covers
- Nominal heating capacity
- 107–164 kW
- Maximum condenser outlet temperature
- 77 °C
- Lowest source inlet temperature
- -20 °C
- Refrigerants
- R290
- Compressor type
- Scroll
- Capacity control
- Frequency controlled
These are the extremes across the range. No single model reaches all of them.
Where EMF fits
Heating
Cooling
DHW
High temperature
- Building systems with a natural-refrigerant strategy
- Low-temperature source circuits
- Heat recovery where source and supply temperatures must be matched
EMF models
2 models from 107 to 164 kW heating. Simulation opens with the EMF machines to choose from. Enter your temperatures and capacity there to see which models cover them.
Find a model for your operating points
Technology
Natural refrigerant: propane (R290)
EMF uses propane (R290), a natural refrigerant; the EMF datasheets publish a GWP of 0.02. Frequency-controlled scroll compressors follow the load.
Propane is safety class A3 (higher flammability). Charge limits, ventilation, gas detection and plant-room layout are resolved for each installation under the applicable standards and local regulations.
Key facts
- R290 (propane), published GWP 0.02
- Safety class A3: refrigerant safety design is part of every project
- Frequency-controlled scroll compressors
- Published limits: source inlet down to −20 °C, condenser outlet up to 77 °C
More about the EMF range
Size and scale
Drawn to scale from the published dimensions. Weights and service clearances are on each model's datasheet.

- Shown
- 2140-2-8
- H × L × W
- 1,743 × 1,050 × 795 mm
- Person for scale
- 1,800 mm
Machine views
Angled view
Can I combine the 60 Hz COP with maximum capacity?
No. The datasheet gives capacity at 30 and 140 Hz and COP at 60 and 140 Hz, so there is no capacity at 60 Hz and no COP at 30 Hz. Use figures from the same speed and duty point.
- R290 propane heat pumps for buildings and industry
- Recovering low-grade heat for useful heating
- How to read our ratingsWhat the rated figures include, and why rated temperatures are not operating limits.