Engineering guidance
Heat pumps for district heating
A district-heating heat pump lifts heat from an available source to the network’s supply temperature. Select it from the network’s supply and return temperatures across the year and the source’s availability, not from a single design point.
Define the network interface
Get the network supply and return temperatures by season. Supply temperature is usually highest in winter; check the temperature lift at that operating case first. A low-temperature network and a high-temperature winter duty are different selections, so check both.
At the connection, record the allowable flow, the heat-exchanger approach and the pressure boundary between the heat-pump circuit and the network. Decide what provides backup heat and how the network takes surplus heat when demand is low.
Source availability and system energy
Start from what the source can deliver: fluid, temperatures and flow, hour by hour if it follows a process or a cooling load. Include source-side and network pumping in the energy estimate; the heat-pump COP leaves them out.
EMT suits larger heating and cooling duties that need continuous capacity control. EMHP is the family to evaluate when the network’s supply temperature drives the selection. The table below lists their datasheet points.
Reference: Sønderjylland Hospital
At Sønderjylland Hospital in Sønderborg, Denmark, two EMT heat pumps with a combined 2.6 MW replaced oil burners and chillers. Waste heat now covers the hospital’s heating and cooling, and 15,800 MWh of surplus heat a year goes to the district heating network. These are reported figures for that installation; another network needs its own selection.
What to send for a network selection
- Network supply and return temperatures through the year, with flow and pressure limits at the connection.
- Source fluid, temperatures and available flow, with the daily and seasonal profile.
- Heat demand profile, backup heat and how surplus heat is handled.
Models and documented rating conditions
Rating points as printed in each datasheet. They describe one operating case each, not the operating envelope. Where a datasheet omits the electrical boundary, load or speed, the row says so.
| Model / refrigerant | Source inlet → outlet | Heated water inlet → outlet | Declared duty | Thermal capacity / COP | Document / boundary |
|---|---|---|---|---|---|
| EMHP 36-36-2-4 R1234ze | ethanol 26% 1 → -3 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 85 kW COP: Withheld pending confirmation | Datasheet V7.0 · 2026-03-05 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMHP 36-36-2-7 R515B | ethanol 26% 1 → -3 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 85 kW COP: Withheld pending confirmation | Datasheet V7.0 · 2026-03-05 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMHP 36F-36F-2-4 R1234ze | ethanol 26% 1 → -3 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 100 kW COP: Withheld pending confirmation | Datasheet V7.0 · 2026-03-05 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMHP 36F-36F-2-7 R515B | ethanol 26% 1 → -3 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 100 kW COP: Withheld pending confirmation | Datasheet V7.0 · 2026-03-05 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMHP 44-44-2-4 R1234ze | ethanol 26% 1 → -3 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 98 kW COP: Withheld pending confirmation | Datasheet V7.0 · 2026-03-05 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMHP 44-44-2-7 R515B | ethanol 26% 1 → -3 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 98 kW COP: Withheld pending confirmation | Datasheet V7.0 · 2026-03-05 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMHP 44F-44F-2-4 R1234ze | ethanol 26% 1 → -3 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 116 kW COP: Withheld pending confirmation | Datasheet V7.0 · 2026-03-05 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMHP 44F-44F-2-7 R515B | ethanol 26% 1 → -3 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 116 kW COP: Withheld pending confirmation | Datasheet V7.0 · 2026-03-05 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMHP 60-60-2-4 R1234ze | ethanol 26% 1 → -3 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 135 kW COP: Withheld pending confirmation | Datasheet V7.0 · 2026-03-05 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMHP 60-60-2-7 R515B | ethanol 26% 1 → -3 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 135 kW COP: Withheld pending confirmation | Datasheet V7.0 · 2026-03-05 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMHP 60F-60F-2-4 R1234ze | ethanol 26% 1 → -3 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 161 kW COP: Withheld pending confirmation | Datasheet V7.0 · 2026-03-05 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMHP 60F-60F-2-7 R515B | ethanol 26% 1 → -3 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 161 kW COP: Withheld pending confirmation | Datasheet V7.0 · 2026-03-05 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMHP 80-80-2-4 R1234ze | ethanol 26% 1 → -3 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 181 kW COP: Withheld pending confirmation | Datasheet V7.0 · 2026-03-05 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMHP 80-80-2-7 R515B | ethanol 26% 1 → -3 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 181 kW COP: Withheld pending confirmation | Datasheet V7.0 · 2026-03-05 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMHP 80F-80F-2-4 R1234ze | ethanol 26% 1 → -3 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 216 kW COP: Withheld pending confirmation | Datasheet V7.0 · 2026-03-05 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMHP 80F-80F-2-7 R515B | ethanol 26% 1 → -3 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 216 kW COP: Withheld pending confirmation | Datasheet V7.0 · 2026-03-05 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMT 1230-1-4-ECO R1234ze | water 12 → 7 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 265 kW COP: Withheld pending confirmation | Datasheet V1.8 · 2025-12-04 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMT 1230-1-7-ECO R515B | water 12 → 7 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 265 kW COP: Withheld pending confirmation | Datasheet V1.8 · 2025-12-04 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMT 1285-1-4-ECO R1234ze | water 12 → 7 °C | water 57 → 63 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 347 kW COP: Withheld pending confirmation | Datasheet V1.8 · 2025-12-04 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMT 1285-1-7-ECO R515B | water 12 → 7 °C | water 57 → 63 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 347 kW COP: Withheld pending confirmation | Datasheet V1.8 · 2025-12-04 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMT 1310-1-4-ECO R1234ze | water 12 → 7 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 379 kW COP: Withheld pending confirmation | Datasheet V1.8 · 2025-12-04 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMT 1310-1-7-ECO R515B | water 12 → 7 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 379 kW COP: Withheld pending confirmation | Datasheet V1.8 · 2025-12-04 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMT 1380-1-4-ECO R1234ze | water 12 → 7 °C | water 57 → 63 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 476 kW COP: Withheld pending confirmation | Datasheet V1.8 · 2025-12-04 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMT 1380-1-7-ECO R515B | water 12 → 7 °C | water 57 → 63 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 476 kW COP: Withheld pending confirmation | Datasheet V1.8 · 2025-12-04 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMT 1490-1-4-ECO R1234ze | water 12 → 7 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 589 kW COP: Withheld pending confirmation | Datasheet V1.8 · 2025-12-04 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMT 1490-1-7-ECO R515B | water 12 → 7 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 589 kW COP: Withheld pending confirmation | Datasheet V1.8 · 2025-12-04 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMT 2230-1-4-FT R1234ze | water 12 → 7 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 530 kW COP: Withheld pending confirmation | Datasheet V1.8 · 2025-12-04 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMT 2230-1-7-FT R515B | water 12 → 7 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 530 kW COP: Withheld pending confirmation | Datasheet V1.8 · 2025-12-04 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMT 2230-2-4-ECO R1234ze | water 12 → 7 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 530 kW COP: Withheld pending confirmation | Datasheet V1.8 · 2025-12-04 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMT 2230-2-7-ECO R515B | water 12 → 7 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 530 kW COP: Withheld pending confirmation | Datasheet V1.8 · 2025-12-04 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMT 2285-1-4-FT R1234ze | water 12 → 7 °C | water 57 → 63 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 694 kW COP: Withheld pending confirmation | Datasheet V1.7 · 2024-12-23 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMT 2285-1-7-FT R515B | water 12 → 7 °C | water 57 → 63 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 694 kW COP: Withheld pending confirmation | Datasheet V1.7 · 2024-12-23 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMT 2285-2-4-ECO R1234ze | water 12 → 7 °C | water 57 → 63 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 694 kW COP: Withheld pending confirmation | Datasheet V1.7 · 2024-12-23 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMT 2285-2-7-ECO R515B | water 12 → 7 °C | water 57 → 63 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 694 kW COP: Withheld pending confirmation | Datasheet V1.7 · 2024-12-23 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMT 2310-1-4-FT R1234ze | water 12 → 7 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 758 kW COP: Withheld pending confirmation | Datasheet V1.7 · 2024-12-23 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMT 2310-1-7-FT R515B | water 12 → 7 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 758 kW COP: Withheld pending confirmation | Datasheet V1.7 · 2024-12-23 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMT 2310-2-4-ECO R1234ze | water 12 → 7 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 758 kW COP: Withheld pending confirmation | Datasheet V1.7 · 2024-12-23 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMT 2310-2-7-ECO R515B | water 12 → 7 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 758 kW COP: Withheld pending confirmation | Datasheet V1.7 · 2024-12-23 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMT 2380-1-4-FT R1234ze | water 12 → 7 °C | water 57 → 63 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 951 kW COP: Withheld pending confirmation | Datasheet V1.7 · 2024-12-23 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMT 2380-1-7-FT R515B | water 12 → 7 °C | water 57 → 63 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 951 kW COP: Withheld pending confirmation | Datasheet V1.7 · 2024-12-23 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMT 2380-2-4-ECO R1234ze | water 12 → 7 °C | water 57 → 63 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 951 kW COP: Withheld pending confirmation | Datasheet V1.7 · 2024-12-23 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMT 2380-2-7-ECO R515B | water 12 → 7 °C | water 57 → 63 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 951 kW COP: Withheld pending confirmation | Datasheet V1.7 · 2024-12-23 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMT 2490-1-4-FT R1234ze | water 12 → 7 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 1,178 kW COP: Withheld pending confirmation | Datasheet V1.7 · 2024-12-23 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMT 2490-1-7-FT R515B | water 12 → 7 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 1,178 kW COP: Withheld pending confirmation | Datasheet V1.7 · 2024-12-23 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMT 2490-2-4-ECO R1234ze | water 12 → 7 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 1,178 kW COP: Withheld pending confirmation | Datasheet V1.7 · 2024-12-23 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMT 2490-2-7-ECO R515B | water 12 → 7 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 1,178 kW COP: Withheld pending confirmation | Datasheet V1.7 · 2024-12-23 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMT 3285-1-4-FT R1234ze | water 12 → 7 °C | water 57 → 63 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 1,041 kW COP: Withheld pending confirmation | Datasheet V1.8 · 2025-12-04 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMT 3285-1-7-FT R515B | water 12 → 7 °C | water 57 → 63 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 1,041 kW COP: Withheld pending confirmation | Datasheet V1.8 · 2025-12-04 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMT 4230-1-4-FT R1234ze | water 12 → 7 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 1,060 kW COP: Withheld pending confirmation | Datasheet V1.7 · 2024-12-23 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMT 4230-1-7-FT R515B | water 12 → 7 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 1,060 kW COP: Withheld pending confirmation | Datasheet V1.7 · 2024-12-23 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMT 4285-1-4-FT R1234ze | water 12 → 7 °C | water 57 → 63 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 1,388 kW COP: Withheld pending confirmation | Datasheet V1.7 · 2024-12-23 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMT 4285-1-7-FT R515B | water 12 → 7 °C | water 57 → 63 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 1,388 kW COP: Withheld pending confirmation | Datasheet V1.7 · 2024-12-23 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMT 4310-1-4-FT R1234ze | water 12 → 7 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 1,516 kW COP: Withheld pending confirmation | Datasheet V1.7 · 2024-12-23 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMT 4310-1-7-FT R515B | water 12 → 7 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 1,516 kW COP: Withheld pending confirmation | Datasheet V1.7 · 2024-12-23 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMT 4380-1-4-FT R1234ze | water 12 → 7 °C | water 57 → 63 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 1,902 kW COP: Withheld pending confirmation | Datasheet V1.7 · 2024-12-23 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMT 4380-1-7-FT R515B | water 12 → 7 °C | water 57 → 63 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 1,902 kW COP: Withheld pending confirmation | Datasheet V1.7 · 2024-12-23 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMT 4490-1-4-FT R1234ze | water 12 → 7 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 2,356 kW COP: Withheld pending confirmation | Datasheet V1.7 · 2024-12-23 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMT 4490-1-7-FT R515B | water 12 → 7 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 2,356 kW COP: Withheld pending confirmation | Datasheet V1.7 · 2024-12-23 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |