EMHP

36-36-2-4

Product Family:
EMHP
Certification:
CE
Refrigerant Type:
R1234ze
Safety Class:
A2L
Capacity Control:
Frequency controlled, PWM

Application

Nominal Heating Capacity:
85 kW
Nominal Cooling Capacity:
121 kW
Nominal COP Heating:
3.22
Nominal COP Cooling:
3.87
Condenser Outlet Temp.:
90 °C
Evaporator Inlet Temp.:
-5 °C
Lowest Evaporator Temp. To Reach Highest Condenser Temp.:
0 °C
Highest Evaporator Outlet Temp.:
35 °C

Dimensions

Length:
2950 mm
Width:
1160 mm
Height:
1845 mm
Weight:
2950 kg

Technical Features

Compressor Type:
Reciprocating
Energy Source:
Ground, Waste heat, Water
Special Features:
Frequency option, High capacity control range, Internal pumps
GWP:
1.37

This Energy Machines™ EMHP model contains two refrigerant circuits with a semi-hermetic reciprocating compressor in each. The two refrigerant circuits are completely independent, ensuring the stability of the heating supply.

The EMHP model is specifically designed for heating and cooling purposes. It can handle large pressure drops on the water side using the machine’s internal water pumps.

The EMHP comes as a complete heat pump and cooling system in one unit.

Documentation

Check an operating point

Indicative — engineering review
Cold side (source)
Hot side (sink)
Up to date

Operating envelope

-15 °C-10 °C-5 °C0 °C5 °C10 °C15 °C20 °C25 °C30 °C35 °C20 °C30 °C40 °C50 °C60 °C70 °C80 °C90 °C100 °CTe – evaporating temperatureTc – condensing temperatureCOP 2COP 3COP 4COP 5COP 6COP 71COP 3.22 · 85 kW

Operating points

Columns
Inputs
Results
Remembered in this browser.
PointSource in → outSink in → outLoadTe / TcHeating capacityElectrical inputCOP heatingActions
110.0 → 7.0 °C40.0 → 45.0 °C100 %4.0 / 48.0 °C85 kW26 kW3.22
Indicative values. Engineering review required.

The EMHP 36-36-2-4 is a reciprocating-compressor heat pump on R1234ze (safety class A2L). Catalogue nominal heating capacity: 85 kW. Catalogue maximum condenser outlet: 90 °C (not verified by this datasheet).

Need an A1 refrigerant? The EMHP 36-36-2-7 is the R515B variant. Both share one datasheet performance table, which shows no performance advantage for either. Confirm site and safety requirements with engineering.

Rating conditions

Rating conditions
Mode / configurationSource fluid in → outSink fluid in → outSpeed / load pointCapacityElectrical input / boundaryCOPDatasheet revision
Datasheet rating points are awaiting engineering confirmation. Request a confirmed operating point for your project.

Source is the evaporator side and sink the condenser side, in both modes. Electrical input is compressor power at the rated point, not the value for sizing the supply. The datasheet names no test standard and no simultaneous heating-and-cooling rating.