EMT

1285-1-7-ECO

Product Family:
EMT
Certification:
CE
Refrigerant Type:
R515B
Safety Class:
A1
Capacity Control:
Frequency controlled

Application

Nominal Heating Capacity:
347 kW
Nominal Cooling Capacity:
275.5 kW
Nominal COP Heating:
3.68
Nominal COP Cooling:
3.44
Condenser Outlet Temp.:
65 °C
Evaporator Inlet Temp.:
-12 °C
Lowest Evaporator Temp. To Reach Highest Condenser Temp.:
7 °C
Highest Evaporator Outlet Temp.:
27 °C

Dimensions

Length:
2950 mm
Width:
1210 mm
Height:
1945 mm
Weight:
2400 kg

Technical Features

Compressor Type:
Turbo
Energy Source:
Ground, Waste heat, Water
Special Features:
Economizer, Oil-free
GWP:
293

This Energy Machines™ EMT model contains a refrigerant circuit with an oil-free centrifugal compressor. It is classified as a non-positive displacement compressor.

This model is equipped with an economizer heat exchanger, increasing its energy efficiency. The machine’s evaporator and condenser are shell-and-tube heat exchangers. The evaporator operates with a flooded evaporation technique.

These components work together to create a powerful and efficient machine.

Documentation

Check an operating point

Indicative — engineering review
Cold side (source)
Hot side (sink)
Up to date

Operating envelope

-25 °C-20 °C-15 °C-10 °C-5 °C0 °C5 °C10 °C15 °C20 °C25 °C30 °C20 °C30 °C40 °C50 °C60 °C70 °CTe – evaporating temperatureTc – condensing temperatureCOP 3COP 4COP 5COP 6COP 7COP 8COP 91COP 3.68 · 347 kW

Operating points

Columns
Inputs
Results
Remembered in this browser.
PointSource in → outSink in → outLoadTe / TcHeating capacityElectrical inputCOP heatingActions
110.0 → 7.0 °C40.0 → 45.0 °C100 %4.0 / 48.0 °C347 kW94 kW3.68
Indicative values. Engineering review required.

The EMT 1285-1-7-ECO is a turbo-compressor heat pump on R515B (safety class A1). Catalogue nominal heating capacity: 347 kW. Catalogue maximum condenser outlet: 65 °C (not verified by this datasheet).

Does the project accept an A2L refrigerant? The EMT 1285-1-4-ECO is the R1234ze variant. Both share one datasheet performance table, which shows no performance advantage for either. Confirm site and safety requirements with engineering.

Rating conditions

Rating conditions
Mode / configurationSource fluid in → outSink fluid in → outSpeed / load pointCapacityElectrical input / boundaryCOPDatasheet revision
Datasheet rating points are awaiting engineering confirmation. Request a confirmed operating point for your project.

Source is the evaporator side and sink the condenser side, in both modes. Electrical input is compressor power at the rated point, not the value for sizing the supply. The datasheet names no test standard and no simultaneous heating-and-cooling rating.