What the datasheets cover

The EMHP heating points in the table below use 26% ethanol at 1 → −3 °C on the cold side (source) and water at 47 → 53 °C on the hot side (sink). Capacity and COP apply to that operating case only. The datasheets do not confirm operation at 90 °C, and a COP from the 47 → 53 °C point cannot be carried over to a 90 °C supply.

For a 90 °C duty, ask for a selection that states the operating map of the chosen model: minimum source temperature, maximum return temperature and flow limits. Steam generation is outside the scope of this guide.

Keep the temperature lift as low as the process allows

Compressor work rises as the condensing temperature goes up and the evaporating temperature goes down. Specify the lowest supply temperature that serves the process, and give the return temperature with it.

The lift the compressor sees is between the refrigerant condensing and evaporating temperatures. It is larger than the difference between hot-side supply and cold-side outlet, because each heat exchanger adds an approach temperature.

In a district network the supply temperature changes through the year, so treat winter and summer as separate operating cases. In a process, keep incompatible fluids apart with a separating heat exchanger, and decide early whether a separate final temperature boost is needed.

What to send for a 90 °C selection

Give these for each operating case: winter design, summer design and typical part load.

  • Hot side: required supply and return temperatures, heat load and annual load profile.
  • Cold side: fluid and concentration, inlet and outlet temperatures, available flow.
  • Site: hydraulic separation, fouling allowance, available electrical supply and auxiliary loads.
  • Constraints: refrigerant siting limits, redundancy, service access and control interfaces.

Models and documented rating conditions

Rating points as printed in each datasheet. They describe one operating case each, not the operating envelope. Where a datasheet omits the electrical boundary, load or speed, the row says so.

Temperatures are fluid inlet → outlet in °C, capacity in kW. Compare rows only at the same temperatures and boundary.
Model / refrigerantSource inlet → outletHeated water inlet → outletDeclared dutyThermal capacity / COPDocument / boundary
EMHP 36-36-2-4
R1234ze
ethanol 26%
1 → -3 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
85 kW
COP: Withheld pending confirmation
Datasheet V7.0 · 2026-03-05 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMHP 36-36-2-7
R515B
ethanol 26%
1 → -3 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
85 kW
COP: Withheld pending confirmation
Datasheet V7.0 · 2026-03-05 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMHP 36F-36F-2-4
R1234ze
ethanol 26%
1 → -3 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
100 kW
COP: Withheld pending confirmation
Datasheet V7.0 · 2026-03-05 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMHP 36F-36F-2-7
R515B
ethanol 26%
1 → -3 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
100 kW
COP: Withheld pending confirmation
Datasheet V7.0 · 2026-03-05 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMHP 44-44-2-4
R1234ze
ethanol 26%
1 → -3 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
98 kW
COP: Withheld pending confirmation
Datasheet V7.0 · 2026-03-05 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMHP 44-44-2-7
R515B
ethanol 26%
1 → -3 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
98 kW
COP: Withheld pending confirmation
Datasheet V7.0 · 2026-03-05 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMHP 44F-44F-2-4
R1234ze
ethanol 26%
1 → -3 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
116 kW
COP: Withheld pending confirmation
Datasheet V7.0 · 2026-03-05 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMHP 44F-44F-2-7
R515B
ethanol 26%
1 → -3 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
116 kW
COP: Withheld pending confirmation
Datasheet V7.0 · 2026-03-05 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMHP 60-60-2-4
R1234ze
ethanol 26%
1 → -3 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
135 kW
COP: Withheld pending confirmation
Datasheet V7.0 · 2026-03-05 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMHP 60-60-2-7
R515B
ethanol 26%
1 → -3 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
135 kW
COP: Withheld pending confirmation
Datasheet V7.0 · 2026-03-05 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMHP 60F-60F-2-4
R1234ze
ethanol 26%
1 → -3 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
161 kW
COP: Withheld pending confirmation
Datasheet V7.0 · 2026-03-05 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMHP 60F-60F-2-7
R515B
ethanol 26%
1 → -3 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
161 kW
COP: Withheld pending confirmation
Datasheet V7.0 · 2026-03-05 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMHP 80-80-2-4
R1234ze
ethanol 26%
1 → -3 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
181 kW
COP: Withheld pending confirmation
Datasheet V7.0 · 2026-03-05 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMHP 80-80-2-7
R515B
ethanol 26%
1 → -3 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
181 kW
COP: Withheld pending confirmation
Datasheet V7.0 · 2026-03-05 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMHP 80F-80F-2-4
R1234ze
ethanol 26%
1 → -3 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
216 kW
COP: Withheld pending confirmation
Datasheet V7.0 · 2026-03-05 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMHP 80F-80F-2-7
R515B
ethanol 26%
1 → -3 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
216 kW
COP: Withheld pending confirmation
Datasheet V7.0 · 2026-03-05 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated