Engineering guidance
Selecting a heat pump for 90 °C hot water
Start with the EMHP family. Its datasheets rate heating at 47 → 53 °C, not 90 °C, so a 90 °C duty needs a project selection at your own source and return temperatures.
What the datasheets cover
The EMHP heating points in the table below use 26% ethanol at 1 → −3 °C on the cold side (source) and water at 47 → 53 °C on the hot side (sink). Capacity and COP apply to that operating case only. The datasheets do not confirm operation at 90 °C, and a COP from the 47 → 53 °C point cannot be carried over to a 90 °C supply.
For a 90 °C duty, ask for a selection that states the operating map of the chosen model: minimum source temperature, maximum return temperature and flow limits. Steam generation is outside the scope of this guide.
Keep the temperature lift as low as the process allows
Compressor work rises as the condensing temperature goes up and the evaporating temperature goes down. Specify the lowest supply temperature that serves the process, and give the return temperature with it.
The lift the compressor sees is between the refrigerant condensing and evaporating temperatures. It is larger than the difference between hot-side supply and cold-side outlet, because each heat exchanger adds an approach temperature.
In a district network the supply temperature changes through the year, so treat winter and summer as separate operating cases. In a process, keep incompatible fluids apart with a separating heat exchanger, and decide early whether a separate final temperature boost is needed.
What to send for a 90 °C selection
Give these for each operating case: winter design, summer design and typical part load.
- Hot side: required supply and return temperatures, heat load and annual load profile.
- Cold side: fluid and concentration, inlet and outlet temperatures, available flow.
- Site: hydraulic separation, fouling allowance, available electrical supply and auxiliary loads.
- Constraints: refrigerant siting limits, redundancy, service access and control interfaces.
Models and documented rating conditions
Rating points as printed in each datasheet. They describe one operating case each, not the operating envelope. Where a datasheet omits the electrical boundary, load or speed, the row says so.
| Model / refrigerant | Source inlet → outlet | Heated water inlet → outlet | Declared duty | Thermal capacity / COP | Document / boundary |
|---|---|---|---|---|---|
| EMHP 36-36-2-4 R1234ze | ethanol 26% 1 → -3 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 85 kW COP: Withheld pending confirmation | Datasheet V7.0 · 2026-03-05 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMHP 36-36-2-7 R515B | ethanol 26% 1 → -3 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 85 kW COP: Withheld pending confirmation | Datasheet V7.0 · 2026-03-05 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMHP 36F-36F-2-4 R1234ze | ethanol 26% 1 → -3 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 100 kW COP: Withheld pending confirmation | Datasheet V7.0 · 2026-03-05 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMHP 36F-36F-2-7 R515B | ethanol 26% 1 → -3 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 100 kW COP: Withheld pending confirmation | Datasheet V7.0 · 2026-03-05 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMHP 44-44-2-4 R1234ze | ethanol 26% 1 → -3 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 98 kW COP: Withheld pending confirmation | Datasheet V7.0 · 2026-03-05 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMHP 44-44-2-7 R515B | ethanol 26% 1 → -3 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 98 kW COP: Withheld pending confirmation | Datasheet V7.0 · 2026-03-05 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMHP 44F-44F-2-4 R1234ze | ethanol 26% 1 → -3 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 116 kW COP: Withheld pending confirmation | Datasheet V7.0 · 2026-03-05 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMHP 44F-44F-2-7 R515B | ethanol 26% 1 → -3 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 116 kW COP: Withheld pending confirmation | Datasheet V7.0 · 2026-03-05 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMHP 60-60-2-4 R1234ze | ethanol 26% 1 → -3 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 135 kW COP: Withheld pending confirmation | Datasheet V7.0 · 2026-03-05 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMHP 60-60-2-7 R515B | ethanol 26% 1 → -3 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 135 kW COP: Withheld pending confirmation | Datasheet V7.0 · 2026-03-05 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMHP 60F-60F-2-4 R1234ze | ethanol 26% 1 → -3 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 161 kW COP: Withheld pending confirmation | Datasheet V7.0 · 2026-03-05 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMHP 60F-60F-2-7 R515B | ethanol 26% 1 → -3 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 161 kW COP: Withheld pending confirmation | Datasheet V7.0 · 2026-03-05 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMHP 80-80-2-4 R1234ze | ethanol 26% 1 → -3 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 181 kW COP: Withheld pending confirmation | Datasheet V7.0 · 2026-03-05 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMHP 80-80-2-7 R515B | ethanol 26% 1 → -3 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 181 kW COP: Withheld pending confirmation | Datasheet V7.0 · 2026-03-05 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMHP 80F-80F-2-4 R1234ze | ethanol 26% 1 → -3 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 216 kW COP: Withheld pending confirmation | Datasheet V7.0 · 2026-03-05 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMHP 80F-80F-2-7 R515B | ethanol 26% 1 → -3 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 216 kW COP: Withheld pending confirmation | Datasheet V7.0 · 2026-03-05 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |