Are the rating temperatures operating limits?

No. The design temperatures on a datasheet describe specific rated duties. The datasheet does not verify the operating envelope shown in the catalogue.

Ask us for the operating-envelope document for your source and sink temperatures. No separate simultaneous-mode rating is stated.

Does the electrical input cover the complete installation?

No. Where a datasheet gives an electrical input at a rated point, as the EMA and EMB datasheets do, it is labelled for the compressors. It is not the input of the complete installed system with all external pumps and auxiliaries.

Use the printed duty, and confirm the system boundary before you use the figure in energy calculations.

What do the EMT and EMHP datasheets leave out?

The EMT and EMHP performance tables do not give the electrical input at the rated point, the compressor speed or load, or the test standard.

The electrical sizing power and supply frequency on a datasheet are for sizing the supply; they are not rated figures. Ask us for the missing figures before you fix a design.