Reading the EMF datasheets

The EMF heating points use 26% ethanol at 1 → −3 °C on the cold side (source) and water at 47 → 53 °C on the hot side (sink). All documented duties use a liquid source; an air coil or other source interface is a separate design.

The compressors are frequency-controlled scrolls, and the sheets print a 30–140 Hz speed range. Keep speed and temperatures the same when you compare models, and watch three points:

  • The capacity range is read as the 30 Hz and 140 Hz endpoints. Confirm that reading before you use an endpoint capacity in a project.
  • The sheets give a COP at 60 Hz but no capacity at 60 Hz. Do not pair that COP with the 140 Hz capacity.
  • Heating and cooling are in separate tables and give no combined efficiency. If you will use both sides at once, ask for that simultaneous operating case.

Site design for an A3 refrigerant

A3 is the higher-flammability class. The installation documentation for the selected unit covers circuit charge, the ventilated enclosure, leak detection and extraction. The factory enclosure does not settle the building side: plant-room ventilation, discharge location, control of ignition sources and maintenance procedures are part of the site design.

Do not work from an assumed charge or a generic separation distance. Get the current installation manual for the selected model and have the site reviewed against it.

Choosing R290

GWP alone does not decide the refrigerant. Safety class, charge, performance at your operating cases and the availability of service for an A3 unit also count. This guide gives no GWP figures; take them from the current datasheet of the selected model.

Models and documented rating conditions

Rating points as printed in each datasheet. They describe one operating case each, not the operating envelope. Where a datasheet omits the electrical boundary, load or speed, the row says so.

Temperatures are fluid inlet → outlet in °C, capacity in kW. Compare rows only at the same temperatures and boundary.
Model / refrigerantSource inlet → outletHeated water inlet → outletDeclared dutyThermal capacity / COPDocument / boundary
EMF 2140-2-8
R290
ethanol 26%
1 → -3 °C
water
47 → 53 °C
Heating
60 Hz
Load: Not stated
No subcooler / standard configuration
Not stated
COP: Withheld pending confirmation
Datasheet V3.0 · 2026-03-06 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMF 2140-2-8
R290
ethanol 26%
1 → -3 °C
water
47 → 53 °C
Heating
140 Hz
Load: Not stated
No subcooler / standard configuration

Endpoint of the printed 30–140 Hz range; confirm interpretation for project selection.

107 kW
COP: Withheld pending confirmation
Datasheet V3.0 · 2026-03-06 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMF 2220-2-8
R290
ethanol 26%
1 → -3 °C
water
47 → 53 °C
Heating
60 Hz
Load: Not stated
No subcooler / standard configuration
Not stated
COP: Withheld pending confirmation
Datasheet V3.0 · 2026-03-06 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMF 2220-2-8
R290
ethanol 26%
1 → -3 °C
water
47 → 53 °C
Heating
140 Hz
Load: Not stated
No subcooler / standard configuration

Endpoint of the printed 30–140 Hz range; confirm interpretation for project selection.

164 kW
COP: Withheld pending confirmation
Datasheet V3.0 · 2026-03-06 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated

Related