EMA

4480-2-7

Product Family:
EMA
Certification:
CE
Refrigerant Type:
R515B
Safety Class:
A1
Capacity Control:
4-Stepped

Application

Nominal Heating Capacity:
464 kW
Nominal Cooling Capacity:
582 kW
Nominal COP Heating:
3.89
Nominal COP Cooling:
5.57
Condenser Outlet Temp.:
65 °C
Evaporator Inlet Temp.:
-4 °C
Lowest Evaporator Temp. To Reach Highest Condenser Temp.:
0 °C
Highest Evaporator Outlet Temp.:
20 °C

Dimensions

Length:
2950 mm
Width:
1170 mm
Height:
2000 mm
Weight:
3000 kg

Technical Features

Compressor Type:
Scroll
Energy Source:
Ground, Water
Special Features:
Internal pumps, Subcooler
GWP:
293

This Energy Machines™ EMA model contains two refrigerant circuits with two compressors in each and a single evaporator and condenser. It offers an optional subcooling feature, allowing for efficient heat energy recovery between the condenser and expansion valve. This results in higher performance due to a greater energy uptake in the machine’s evaporator process.

The EMA is designed to handle large pressure drops on the chilled and warm side using the machine’s internal water pumps.

The EMA comes as a completely reversible heat pump in one unit.

Documentation

Check an operating point

Indicative — engineering review
Cold side (source)
Hot side (sink)
Up to date

Operating envelope

-15 °C-10 °C-5 °C0 °C5 °C10 °C15 °C20 °C20 °C30 °C40 °C50 °C60 °C70 °CTe – evaporating temperatureTc – condensing temperatureCOP 3COP 4COP 5COP 6COP 7COP 8COP 91COP 3.89 · 464 kW

Operating points

Columns
Inputs
Results
Remembered in this browser.
PointSource in → outSink in → outLoadTe / TcHeating capacityElectrical inputCOP heatingActions
110.0 → 7.0 °C40.0 → 45.0 °C100 %4.0 / 48.0 °C464 kW119 kW3.89
Indicative values. Engineering review required.

The EMA 4480-2-7 is a scroll-compressor heat pump on R515B (safety class A1). With the subcooler it delivers 464 kW of heat at 1 °C → -3 °C ethanol 26% on the source side and 47 °C → 53 °C water on the sink side. Catalogue maximum condenser outlet: 65 °C (not verified by this datasheet).

Does the project accept an A2L refrigerant? The EMA 4480-2-4 is the R1234ze variant. Both share one datasheet performance table, which shows no performance advantage for either. Confirm site and safety requirements with engineering.

Rating conditions

4 rated points · datasheet V4.0

Rated points from datasheet V4.0 (2025-12-02). These are rating conditions, not operating limits.

Rating conditions
Mode / configurationSource fluid in → outSink fluid in → outSpeed / load pointCapacityElectrical input / boundaryCOPDatasheet revision
Heating
Without subcooler
ethanol 26%
1 °C → -3 °C
water
47 °C → 53 °C
4 compressors347 kW119.4 kW
Compressors only
2.91V4.0
2025-12-02
Heating
With subcoolerSubcooler: 7 °C → 39 °C (fluid not stated)
ethanol 26%
1 °C → -3 °C
water
47 °C → 53 °C
4 compressors464 kW119.4 kW
Compressors only
3.89V4.0
2025-12-02
Cooling
Without subcooler
ethanol 26%
16 °C → 10 °C
water
37 °C → 43 °C
4 compressors438 kW104.6 kW
Compressors only
4.19V4.0
2025-12-02
Cooling
With subcoolerSubcooler: 7 °C → 29 °C (fluid not stated)
ethanol 26%
16 °C → 10 °C
water
37 °C → 43 °C
4 compressors582 kW104.6 kW
Compressors only
5.57V4.0
2025-12-02

Source is the evaporator side and sink the condenser side, in both modes. Electrical input is compressor power at the rated point, not the value for sizing the supply. The datasheet names no test standard and no simultaneous heating-and-cooling rating.